The Problem with Dormant Drinking Fountains
When buildings have little to no water use for an extended period of time, water can sit stagnant in plumbing lines and fixtures. This can create water quality concerns, including the potential growth of Legionella bacteria and increased levels of lead and copper from corroded plumbing.
Before returning drinking fountains, water coolers, and bottle fillers to regular use, it’s important to flush the building’s water system and individual fixtures. Filters and other components may also need attention before the units are put back into service.
This article covers the steps involved in flushing drinking fountains after an extended period of inactivity, along with manufacturer-specific recommendations from two of the leading drinking fountain manufacturers we carry at Equiparts: Oasis and Elkay.
Step 1: Flush the Building’s Water System
Before flushing individual drinking fountains and water coolers, the building’s plumbing system should be addressed first. Flushing an individual fixture does not replace the need to flush the building’s water lines.
Building owners and maintenance teams should review their water management procedures and follow CDC and EPA recommendations for restoring water quality after a prolonged shutdown or period of reduced use.
Here are a few resources with additional information:
- CDC: Reopening Buildings After Prolonged Shutdown or Reduced Operation
- EPA: Information on Maintaining or Restoring Water Quality in Buildings with Low or No Use
- AWWA: Responding to Water Stagnation in Buildings with Reduced or No Water Use
The CDC recommends flushing hot and cold water through all points of use, including faucets and other fixtures. Depending on the size of the building and its plumbing configuration, flushing may need to be completed in sections.
Take care to minimize splashing and aerosol generation during flushing. Facilities should also follow their water management plan and document any maintenance activities.
Step 2: Inspect Drinking Fountains, Water Coolers & Bottle Fillers
Once the building’s water system has been addressed, move on to the individual drinking fountains, water coolers, and bottle fillers.
Before flushing each unit, inspect the fixture for visible leaks, damaged water lines, or signs of buildup around the dispensing area. Check the condition of filters and review their replacement dates. Filters that have been in service or sitting unused for an extended period may need to be replaced.
Different manufacturers have different recommendations for flushing their units. Below are instructions from Oasis and Elkay, two of the top drinking fountain manufacturers we carry at Equiparts.
Oasis Directions for Flushing Fountains
1. Filtered Units
Remove all filters prior to flushing the units. Disconnect the water lines from the filter and reconnect them using a 1/4″ John Guest coupling. Now you’re ready for the flushing procedure.
2. Drinking Fountains and Water Coolers
Turn on water flow through the bubbler for at least 5 minutes. A 10-minute flush time is more than enough.
3. Combination Bottle Filler with Drinking Fountain/Water Cooler
First, flush the bottle filler for at least 5 minutes or longer, if desired. Then flush the drinking fountain or water cooler through the bubbler for at least 5 minutes.
4. Replace Filters
Once you are finished flushing your units, disconnect the John Guest coupling and install a new filter.
For more information, view this video from Oasis:
Cleaning and Sanitizing Your OASIS Water Cooler
– – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – – —
Elkay Directions for Flushing Fountains
Elkay provides different flushing recommendations depending on whether the unit is filtered and how long it has been inactive.
1. Filtered Units – Inactive
If units have been inactive for 4 weeks or more, Elkay’s published guidance recommends replacing the filters because of water stagnation. After the filters are replaced, activate the water stream on each unit for 3 minutes to flush the system.
2. Filtered Units – Active
If maintenance staff have regularly activated the water stream during a facility closure, the filters may not need to be replaced because the water has not been stagnant for an extended period. Activate the water stream on each product for 3 minutes to flush the system.
3. Non-Filtered Units – Active or Inactive
Activate the water stream on each product for 3 minutes to flush the system.
Note: These flushing times reflect previously published manufacturer guidance. Always check the current maintenance instructions for your specific model before performing maintenance. Filter replacement requirements may vary by filter type, usage, and manufacturer recommendations.
Step 3: Clean Drinking Fountains and Bottle Fillers
Once flushing is complete, clean the drinking fountain, bottle filler, and dispensing areas before returning the units to regular use. Pay particular attention to the bubbler, bottle filling nozzle, and other areas that come into contact with water or users.
Cleaning recommendations vary by surface material and fixture type. For step-by-step instructions on cleaning stainless steel, chrome, plastic, and other drinking fountain surfaces, see our guide:
How to Clean a Drinking Fountain: A Step-by-Step Guide
Always follow the manufacturer’s recommendations for cleaning products and sanitizing procedures. Cleaning exterior surfaces does not replace any required internal flushing or sanitizing.
Important Water Safety Considerations
Flushing a drinking fountain or bottle filler does not guarantee that the water is safe to drink. Extended periods of inactivity, plumbing conditions, and water quality concerns may require additional assessment before fixtures are returned to service.
Facilities with known or suspected Legionella contamination, water quality issues, or extended water service disruptions should consult their water management team and follow applicable public health guidance before returning drinking water fixtures to use.
For additional information, refer to the CDC’s guidance for reopening buildings.
Frequently Asked Questions
How long should you flush a drinking fountain after extended inactivity?
Flushing times depend on the manufacturer, model, and filtration system. Oasis has published recommendations of at least 5 minutes for its drinking fountains and bottle fillers, while Elkay’s published guidance recommends 3 minutes for its units. Always refer to the current manufacturer instructions for your specific model.
Should drinking fountain filters be replaced after a building closure?
Filters may need to be replaced after an extended period of inactivity. Check the manufacturer’s recommendations for your specific filter and unit. For example, Elkay’s previously published guidance recommends replacing filters when units have been inactive for four weeks or longer.
Can stagnant water in drinking fountains cause Legionella?
Stagnant water can create conditions that allow Legionella bacteria to grow. Reduced water flow, lower disinfectant levels, and changes in water temperature can contribute to bacterial growth in building plumbing systems. Proper water management and maintenance help minimize these risks.
Do bottle fillers need to be flushed separately from drinking fountains?
Yes. Combination units may have separate dispensing outlets and internal water pathways. Follow the manufacturer’s instructions for flushing both the bottle filler and drinking fountain components.
How often should drinking fountains be flushed when not in use?
Facilities should establish a flushing schedule based on their water management plan, building usage, and manufacturer recommendations. Regular flushing of infrequently used fixtures can help reduce water stagnation.
Need Replacement Filters or Drinking Fountain Parts?
Keeping drinking fountains, water coolers, and bottle fillers properly maintained helps support reliable operation and water quality throughout your facility.
Equiparts carries replacement filters, repair parts, and components for leading drinking fountain manufacturers, including Elkay, Oasis, Halsey Taylor, Murdock, Sloan, and more.
Whether you’re replacing a filter, servicing a bubbler, or getting equipment ready for regular use, our team can help you find the right parts.
Looking for drinking fountain parts or equipment?
Explore our selection of:
Questions? Call our team at 1-800-442-6622, Monday–Friday, 8 a.m.–4 p.m. EST.